1)Cable Fault Detection - Site - Mas Subang
2) Taman Pertanian Malaysia - Relay Calibration - Earth Fault And Overcurrent TYpe CDG and Oil Dashpot
18th & 19th June - Freescale - Commisioning of MSB - 3lots.
20th June- Pulapes,Mentaakab Pahang - Fault Detection due to breakdown
20th June Colgate -Palmolive - Circuit Breaker - ABB - commisioning
21st June - UPM
22nd June- USIM - commisioning of HT,LV, and Transformer.
23rd June- GSC calibration, Jaks Steel Site Visit
24th June - ST Electronics Muar
- Relay Calibration.
25th June - Seremban - Feeder Pillar - Mikro ELR calibration.
Thursday, July 8, 2010
6th June 2010 till 25Th June 2010
Posted by VK at 2:29 AM 0 comments
Tuesday, July 6, 2010
Thursday, June 10, 2010
31st May 2010 till 6th June 2010
1st June,2nd June -
Site - Taman Pertanian Bukit Cahaya
- Feeder Relay Recalibration
- Relay Type Oil Dashpot and CDG.
3rd June -
Site - Tamco & Schneider
Task - Tamco - commisioning for Ban Seng Lee 1incoming on 1 transformer switchboards
- Schneider - Pressure Test on RMU or also known as RM6.
4th June
Site - Mas Cable Fault
- Partial Mas Subang tripped after a contractor tried to dig hole on the cable passage where by caused a puncture and main to trip. Immediate cable fault detection and replacement with new 3phase 10m cooper cable.
Photos below




31st May 2010
Site - UPM Cable Fault - Veterinar Outgoing Cable Puncture
- Replacing puncture cable with new 10m Aluminium 3 phase Cable. 


5th June-
Wisma Pengkalan
- General Maintenance
6th June -
Site - Ban Seng Lee
- Terminal Connection To Transformer Relay and Pressure Test on 11kv Transformer.


Posted by VK at 8:12 AM 0 comments
26th till 28th 29th May - Top Places. Secret Identities.
26th May 2010
Site - Measat
- General Maintenance
- Time 00.00am till 04.30a.m.
27th May 2010
Site - Sime Darby Tennamaram Oil Plant
- Recalibration of SPAJ 140c - Heavy Tripping due to High Starting Amps
- Had Change To Observe Steam Turbine Power Generation.
28th May 2010
Site - Permodalan Nasional Berhad.
- Maintenance on Public Holiday - Wesak Day.
- Service ACB's and had change to observe speed test on VCB's.
29th May 2010
- office
- Relays Calibrations on SPAJ 140c.
Posted by VK at 8:00 AM 0 comments
25th - Sime Darby Nuri Edible Oil Plant
Site: Sime Darby Nuri Edible Oil Plant
Task - Commisioning of LV, HT Side & GenSet Switchboards.
- Learned on Delab Setting of EFR> Earth Fault Relay. - Connections and Primary Injections on CT.
Photos Below -


Posted by VK at 7:52 AM 0 comments
24th April 2010 - Chicken Eggs Anyone
Site - Melaka Chicken Farm
Task - Commisioning new Low Voltage Side switchboards for new Chicken Farm. Type of relays are CDG Relays for earth fault leakage and Oil Dashpots for phase overcurrent. This kind of relays are used so that it does not trip too frequently and only trips when is essential.
This are some photos :



Posted by VK at 7:37 AM 0 comments
Months Days Hours Minutes Seconds Past QuACKLy - 13th till 21st May
13th May 2010 & 14th - Site : Office
- Task : Preparing tools and equipments and updating the service equipments. Learned More on Delab Relay. Type ELR. The Settings are as below
Current Setting 0.03 - 30.00 Ampere
Trip Time Setting - 0.05 - 20.0 (0.1sec step)
High Set - 5~ 50 Ampere
High Set Trip Time - 30ms (fixed)
Output relay = 240 VAC / 5 Ampere
CT Type : ZCT
Posted by VK at 7:15 AM 0 comments